| Frame Size | A |
| Normal Duty Rated Output Capacity (kVA) | 10 |
| Normal Duty Rated Output Current (A) | 12 |
| Normal Duty Applicable Motor Output (kW) | 5.5 |
| Normal Duty Applicable Motor Output (HP) | 7.5 |
| Overload Capacity | 120% of rated current: 1 minute for every 5 minutes; 160% of rated current: 3 seconds for every 30 seconds |
| Max. Output Frequency (Hz) | 0.00 ~ 599.00 |
| Carrier Frequency (kHz) | 2 ~ 15 (default setting 8) |
| Heavy Duty Rated Output Capacity (kVA) | 9.6 |
| Heavy Duty Rated Output Current (A) | 11 |
| Heavy Duty Applicable Motor Output (kW) | 4.0 |
| Heavy Duty Applicable Motor Output (HP) | 5 |
| Overload Capacity | 150% of rated current: 1 minute for every 5 minutes; 180% of rated current: 3 seconds for every 30 seconds |
| Heavy Duty Max. Output Frequency (Hz) | 0.00 ~ 300.00 |
| Carrier Frequency (kHz) | 2 ~ 6 (default setting 2) |
| Input Current Normal Duty | 17 |
| Input Current Heavy Duty | 16 |
| Input Rated Voltage / Frequency | 3-phase AC 200 V ~ 240 V (-15% ~ +10%), 50 / 60 Hz |
| Operating Voltage Range | 323 ~ 528Vac |
| Frequency Tolerance | 47 ~ 63 Hz |
| Drive Weight (Kg) | 2.6 ± 0.3 |
| Efficiency (%) | 97.8 |
| Power Factor | > 0.98 |
| Cooling Method | Fan Cooling |
| Braking Chopper | built-in |
| DC Choke | optional |
| EMC Filter | optional |
| EMC-COP01 | optional |